| STANDARD
PARTICULARS |
| Drawing No. |
|
HC- PN 1103 |
HC- PN 1101 |
HC- PN 1102 |
HC- PN 1104 |
HC- PN 1105 |
| Highest System Voltage |
KV |
12 |
12 |
12 |
12 |
12 |
| Working Voltage |
KV |
11 |
11 |
11 |
11 |
11 |
| Creepage Distance Minimum |
MM |
280 |
230 |
230 |
320 |
320 |
| Visible Discharge Voltage |
KV |
9 |
9 |
9 |
9 |
9 |
| Mechanical Failing Load |
KN |
10 |
5/10 |
5 |
10 |
10 |
| Power Frequency Withstand Voltage |
Wet |
KV |
35 |
35 |
35 |
40 |
40 |
| Dry |
KV |
60 |
40 |
40 |
65 |
65 |
| Power Frequency Flashover Voltage |
Wet |
KV |
40 |
40 |
40 |
45 |
45 |
| Dry |
KV |
65 |
65 |
65 |
70 |
70 |
| Impulse Withstand Voltage |
KVp |
75 |
75 |
75 |
75 |
75 |
| Puncture Voltage |
KV |
105 |
105 |
105 |
105 |
105 |
| Lead Thimble as per IS : 2486 (Part II) |
|
Small/Large |
Small/Large |
Small |
Small/Large |
Small/Large |
| Net Weight (aaprox) |
Kg. |
1.65 |
1.4 |
1.1 |
2.0 |
1.8 |
| Specification as per IS : 731 ,